DCSA

DCSA20

  • Electrical Characteristics
    • Catalog # DCSA20
    • Output Voltage 10 - 30 Vdc
    • Output Range 4 - 20 mA or 1 to 5 Vdc or 2 to 10 Vdc
    • Momentary Output Voltage (V) 40 for 1 m
    • Output Type Analog current directly proportional to input current
    • Response Time (ms) ≅300 ms
    • Repeat Accuracy (%) ±0.25% of full scale under fixed conditions
    • Current Sensor Range 0 - 20 mA ac; factory calibrated to ±0.5% of full scale
    • Polarity Units are reverse polarity protected
    • Insulation Resistance ≥100
    • Dielectric Breakdown ≥2500 terminals to mounting surface
    • Zero Adjust (mA) ≅3.75 - 4.25 mA
    • Temperature Coefficient (% / C) ±0.05%
    • Termination Type Wire clamp for 22-14 AWG (0.336mm²-2.5mm²)
    • Mounting Method DIN 1 and DIN 3 rail mounting
    • Operating Temperature -30° to 60°C (-22° to 140°F)
    • Storage Temperature (F/C) -40° to 85°C (-40° to 185°F)
    • Humidity 95% non-condensing
    • Weight (lbs/g) 0 Kg
    • Check Stock Yes