ISS 105

ISS-105

  • Electrical Characteristics
    • Catalog # ISS-105
    • Input Voltage (V) 120 Vac
    • Input Tolerance (%) ±10%
    • Maximum Input Power 5
    • Input AC Line Frequency (Hz) 50 / 60 (50 will increase all delay timers by 20%)
    • Output Load Rating (VA) Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 7 A @ 240 Vac
    • Sense Voltage 5 Vdc continuous (probe)
    • Intrinsically Safe Circuit Location Division 1 and 2; Class I Groups A B C D; Class II Groups E F G; Class III
    • Protection Class IP20 (finger safe)
    • Termination Type Torque: 3.5 to 4.5 in-lbs (max. 6 in.-lbs); Wire: 12 - 20 AWG
    • Mounting Method 35mm DIN rail or Surface Mount (#6 or #8 screws)
    • Operating Temperature -40° to 55°C (-40° to 131°F)
    • Humidity 10 - 95% non-condensing per IEC 68-2-3
    • Dimensions 2.35 H x 3.7 W x 5.03 D in. (59.7 x 94.1 x 127.6 mm)
    • Weight (lbs/g) 0 Kg
    • Check Stock Yes