233P

233P-1.5

  • Electrical Characteristics
    • Catalog # 233P-1.5
    • Input Voltage (V) 230VAC
    • Maximum Input Power 5W
    • Input AC Line Frequency (Hz) 50/60Hz (50Hz will increase all delay timers by 20%.)
    • Input Load Range (hp) 1/3 - 1.5 hp
    • Output Form SPST
    • Output Load Rating (VA) 1.5 hp @ 240VAC (10 amps max.)
    • Rapid Cycle Timer (s) 4 restarts allowed in 60s period
    • Restart Delay Range Over/Under Voltage: 2s; All other faults: Manual 2 - 225m
    • Trip Delay Range Overcurrent: 5s; Dry-well: 4s
    • Overvoltage Trip Voltage (%) 265VAC
    • Undervoltage Reset Voltage (%) 190VAC
    • Overcurrent Trip Class 125% of calibration point
    • Underload (%) Adjustable (70 to 90% of calibrated run power)
    • Termination Type Torque: 13 in-lbs; Wire: Stranded or solid 10-22AWG
    • Mounting Method #8 screws
    • Operating Temperature -40° to 55°C (-40° to 131°F)
    • Dimensions 2.93î H x 5.25î W x 2.91î D (73.7 x 133.4 x 74.0 mm)
    • Weight (lbs/g) 0.88 lb. (14.0 oz. 396.9 g)