Motor and Pump Protection

777-KW/HP-P2 Series - 3-Phase Current & Voltage Monitor

  • Electrical Characteristics
    • Catalog # 777-575-KW/HP-P2
    • Input
      Voltage (V)
      500 - 600 Vac
    • Output
      Form
      SPDT - Form C
    • Termination Type Torque: 7 in-lbs
    • Mounting Method Surface mount (4 - #8 screws) or DIN rail mount
    • Full Load Amp Range (A) 2 - 20 (looped conductors required); 20 - 90 (direct); 90 - 800 (external CTs required)
    • Dimensions 3.05 H x 3.85 W x 5.05 D in. (77.5 x 97.8 x 128.3 mm)
    • Weight (lbs/g) 0 Kg
    • Overcurrent Trip Class 02 - 60; J02 - J60; L00 - L60; or OFF
    • Overcurrent Trip Point (20 - 100 A) … MULT of 80 - 140% of CT primary
    • Address COM: C00 - C07; RS-485: A01 - A99
    • Current Accuracy (%) ±3% (<100 A direct)
    • Current Unbalance Trip Point (%) 2 - 50% or 999 (disabled)
    • Ground Fault Accuracy (%) ±15%
    • Ground Fault Current Trip Point (A) (3 - 20) … MULT or 12 - 40% of primary CT or OFF
    • Humidity 10 - 95% non-condensing per IEC 68-2-3
    • Input AC Line Frequency (Hz) 50 / 60
    • Maximum Input Power 10
    • CT Ratio 1 - 10; 100; 150; 200; 300; 400; 500; 600; 700; 800
    • Output Load Rating (VA) Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 10 A @ 240 Vac
    • Overvoltage Trip Voltage (%) 451 - 660 V
    • Pollution Degree 3
    • Power Range Setting Power Scale: 1 = 0.01 - 0.99 kW; 2 = 1.00 - 9.95 kW; 3 = 10.0 - 99.5 kW; 4 = 100 - 650 kW; 5 = 0.01 - 1.32 hp; 6 = 1.34 - 13.3 hp; 7 = 13.4 - 133 hp; 8 = 134 - 871 hp; Low Power: 0.01 - 650 kW or 0.01 - 871 hp or 0 (off); LP setting is dependent on PWS setting; PWS must be set prior to LP setting
    • Protection Class IP20 (finger safe)
    • Rapid Cycle Timer (s) 0 - 999 s
    • Repeat Accuracy (%) Voltage: ±0.5% of nominal voltage; Current: ±1% (<100 A direct); Power: ±2%
    • Restart Delay Range All faults except undercurrent: 0 - 500 s; Undercurrent: 0 - 500 s A (Automatic); # of Restarts: All faults except undercurrent: 0; 1; oc1; 2; oc2; 3; oc3; oc4; A; ocA (Automatic); Undercurrent: 0; 1; 2; 3; 4; A (Automatic)
    • Sensor Hole Size Max conductor size: 0.65 in (with insulation)
    • Short Circuit (kA) 100
    • Storage Temperature (F/C) -40° to 80°C (-40° to 176°F)
    • Surge Protection IEC: 61000-4-5 Level 3 2 kV line-to-line; Level 4 4 kV line-to-ground
    • Timing Accuracy (%) ±0.5 s
    • Undercurrent Trip Delay (s) 5 s (default)
    • Undervoltage Trip Voltage 450 - 649 V
    • Voltage Accuracy (%) ±1%
    • Voltage Unbalance Trip Point (%) 2 - 25% or 999 (disabled)
    • Datasheet
    • Check Stock Order Sample
    • Catalog # 777-HVR-KW/HP-P2
    • Input
      Voltage (V)
      340 - 480 Vac
    • Output
      Form
      SPDT - Form C
    • Termination Type Torque: 7 in-lbs
    • Mounting Method Surface mount (4 - #8 screws) or DIN rail mount
    • Full Load Amp Range (A) 2 - 20 (looped conductors required); 20 - 90 (direct); 90 - 800 (external CTs required)
    • Dimensions 3.05 H x 3.85 W x 5.05 D in. (77.5 x 97.8 x 128.3 mm)
    • Weight (lbs/g) 0 Kg
    • Overcurrent Trip Class 02 - 60; J02 - J60; L00 - L60; or OFF
    • Overcurrent Trip Point (20 - 100 A) … MULT of 80 - 140% of CT primary
    • Address COM: C00 - C07; RS485: A01 - A99
    • Current Accuracy (%) ±3% (<100 A direct)
    • Current Unbalance Trip Point (%) 2 - 50% or 999 (disabled)
    • Ground Fault Accuracy (%) ±15%
    • Ground Fault Current Trip Point (A) (3 - 20) … MULT or 12 - 40% of CT primary or OFF
    • Humidity 10 - 95% non-condensing per IEC 68-2-3
    • Input AC Line Frequency (Hz) 50 / 60
    • Maximum Input Power 10
    • CT Ratio 1 - 10; 100; 150; 200; 300; 400; 500; 600; 700; 800
    • Output Load Rating (VA) Pilot Duty: 470 VA @ 600 Vac B600; General Purpose: 10 A @ 240 Vac
    • Overvoltage Trip Voltage (%) 341 - 528 V
    • Pollution Degree 3
    • Protection Class IP20 (finger safe)
    • Rapid Cycle Timer (s) 0 - 999 s
    • Repeat Accuracy (%) Voltage: ±0.5% of nominal voltage; Current: ±1% (<100 A direct); Power: ±2%
    • Restart Delay Range All faults except undercurrent: 2 - 500 m; Undercurrent: 2 - 500 m A (Automatic); # of Restarts: All faults except undercurrent: 0; 1; oc1; 2; oc2; 3; oc3; 4; oc4; A; ocA (Automatic); Undercurrent: 0; 1; 2; 3; 4; A (Automatic)
    • Sensor Hole Size Max conductor size: 0.65 in (with insulation)
    • Short Circuit (kA) 100
    • Storage Temperature (F/C) -40° to 80°C (-40° to 176°F)
    • Surge Protection IEC: 61000-4-5 Level 3 2 kV line-to-line; Level 4 4 kV line-to-ground
    • Timing Accuracy (%) ±0.5 s
    • Undercurrent Trip Delay (s) 5 s (default)
    • Undervoltage Trip Voltage 340 - 523 V
    • Voltage Accuracy (%) ±1%
    • Voltage Unbalance Trip Point (%) 2 - 25% or 999 (disabled)
    • Datasheet
    • Check Stock Order Sample
    • Catalog # 777-KW/HP-P2
    • Input
      Voltage (V)
      200 - 480 Vac
    • Output
      Form
      SPDT - Form C
    • Termination Type Torque: 7 in-lbs
    • Mounting Method Surface mount (4 - #8 screws) or DIN rail mount
    • Full Load Amp Range (A) 2 - 20 (looped conductors required); 20 - 90 (direct); 90 - 800 (external CTs required)
    • Dimensions 3.05 H x 3.85 W x 5.05 D in. (77.5 x 97.8 x 128.3 mm)
    • Weight (lbs/g) 0 Kg
    • Overcurrent Trip Class 02 - 60; J02 - J60; L00 - L60; or OFF
    • Overcurrent Trip Point (20 - 100 A) … MULT of 80 - 140% of CT primary
    • Address COM: C00 - C07; RS485: A01 - A99
    • Current Accuracy (%) ±3% (<100 A direct)
    • Current Unbalance Trip Point (%) 2 - 50% or 999 (disabled)
    • Ground Fault Accuracy (%) ±15%
    • Ground Fault Current Trip Point (A) (3 - 20) … MULT or 12 - 40% of CT primary or OFF
    • Humidity 10 - 95% non-condensing per IEC 68-2-3
    • Input AC Line Frequency (Hz) 50 / 60
    • Maximum Input Power 10
    • CT Ratio 1 - 10; 100; 150; 200; 300; 400; 500; 600; 700; 800
    • Output Load Rating (VA) Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 10 A @ 240 Vac
    • Overvoltage Trip Voltage (%) 172 - 528 V
    • Pollution Degree 3
    • Power Range Setting Power Scale: 1 = 0.01 - 0.99 kW; 2 = 1.00 - 9.95 kW; 3 = 10.0 - 99.5 kW; 4 = 100 - 650 kW; 5 = 0.01 - 1.32 hp; 6 = 1.34 - 13.3 hp; 7 = 13.4 - 133 hp; 8 = 134 - 871 hp; Low Power: 0.01 - 650 kW or 0.01 - 871 hp or 0 (off); LP setting is dependent on PWS setting; PWS must be set prior to LP setting
    • Protection Class IP20 (finger safe)
    • Rapid Cycle Timer (s) 0 - 999 s
    • Repeat Accuracy (%) Voltage: ±0.5% of nominal voltage; Current: ±1% (<100 A direct); Power: ±2%
    • Restart Delay Range All faults except undercurrent: 2 - 500 m; Undercurrent: 2 - 500 m A (Automatic); # of Restarts: All faults except undercurrent: 0; 1; oc1; 2; oc2; 3; oc3; 4; oc4; A; ocA (Automatic); Undercurrent: 0; 1; 2; 3; 4; A (Automatic)
    • Sensor Hole Size Max conductor size: 0.65 in (with insulation)
    • Short Circuit (kA) 100
    • Storage Temperature (F/C) -40° to 80°C (-40° to 176°F)
    • Surge Protection IEC: 61000-4-5 Level 3 2 kV line-to-line; Level 4 4 kV line-to-ground
    • Timing Accuracy (%) ±0.5 s
    • Undercurrent Trip Delay (s) 5 s (default)
    • Undervoltage Trip Voltage 170 - 524 V
    • Voltage Accuracy (%) ±1%
    • Voltage Unbalance Trip Point (%) 2 - 25% or 999 (disabled)
    • Datasheet
    • Check Stock Order Sample
    • Catalog # 777-LR-KW/HP-P2
    • Input
      Voltage (V)
      200 - 480 Vac
    • Output
      Form
      SPDT - Form C
    • Termination Type Torque: 7 in-lbs
    • Mounting Method Surface mount (4 - #8 screws) or DIN rail mount
    • Full Load Amp Range (A) 1 - 2 (looped conductors required); 2.1 - 9.0 (direct); 10 - 800 (external CTs required)
    • Dimensions 3.05 H x 3.85 W x 5.05 D in. (77.5 x 97.8 x 128.3 mm)
    • Weight (lbs/g) 0 Kg
    • Overcurrent Trip Class 02 - 60; J02 - J60; L00 - L60; or OFF
    • Overcurrent Trip Point (2 - 10 A) … MULT of 80 - 140% of CT primary
    • Address COM: C00 - C07; RS485: A01 - A99
    • Current Accuracy (%) ±3% (<100 A direct)
    • Current Unbalance Trip Point (%) 2 - 50% or 999 (disabled)
    • Ground Fault Accuracy (%) ±15%
    • Ground Fault Current Trip Point (A) (0.3 - 2.0) … MULT or 6 - 40% of CT primary or OFF
    • Humidity 10 - 95% non-condensing per IEC 68-2-3
    • Input AC Line Frequency (Hz) 50 / 60
    • Maximum Input Power 10
    • CT Ratio 1 - 2; 25; 50; 75; 100; 150; 200; 300; 400; 500; 600; 700; 800
    • Output Load Rating (VA) Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 10 A @ 240 Vac
    • Overvoltage Trip Voltage (%) 172 - 528 V
    • Pollution Degree 3
    • Power Range Setting Power Scale: 1 = 0.01 - 0.99 kW; 2 = 1.00 - 9.95 kW; 3 = 10.0 - 99.5 kW; 4 = 100 - 650 kW; 5 = 0.01 - 1.32 hp; 6 = 1.34 - 13.3 hp; 7 = 13.4 - 133 hp; 8 = 134 - 871 hp; Low Power: 0.01 - 650 kW or 0.01 - 871 hp or 0 (off); LP setting is dependent on PWS setting; PWS must be set prior to LP setting
    • Protection Class IP20 (finger safe)
    • Rapid Cycle Timer (s) 0 - 999 s
    • Repeat Accuracy (%) Voltage: ±0.5% of nominal voltage; Current: ±1% (<100 A direct); Power: ±2%
    • Restart Delay Range All faults except undercurrent: 2 - 500 m; Undercurrent: 2 - 500 m A (Automatic); # of Restarts: All faults except undercurrent: 0; 1; oc1; 2; oc2; 3; oc3; 4; oc4; A; ocA (Automatic); Undercurrent: 0; 1; 2; 3; 4; A (Automatic)
    • Sensor Hole Size Max conductor size: 0.65 in (with insulation)
    • Short Circuit (kA) 100
    • Storage Temperature (F/C) -40° to 80°C (-40° to 176°F)
    • Surge Protection IEC: 61000-4-5 Level 3 2 kV line-to-line; Level 4 4 kV line-to-ground
    • Timing Accuracy (%) ±0.5 s
    • Undercurrent Trip Delay (s) 5 s (default)
    • Undervoltage Trip Voltage 170 - 524 V
    • Voltage Accuracy (%) ±1%
    • Voltage Unbalance Trip Point (%) 2 - 25% or 999 (disabled)
    • Datasheet
    • Check Stock Order Sample
    • Catalog # 777-MLR-KW/HP-P2
    • Input
      Voltage (V)
      200 - 480 Vac
    • Output
      Form
      SPDT - Form C
    • Termination Type Torque: 7 in-lbs
    • Mounting Method Surface mount (4 - #8 screws) or DIN rail mount
    • Full Load Amp Range (A) 0.5 - 5 (looped conductors required); 5 - 21 (direct); 40 -740 (external CTs required)
    • Dimensions 3.05 H x 3.85 W x 5.05 D in. (77.5 x 97.8 x 128.3 mm)
    • Weight (lbs/g) 0 Kg
    • Overcurrent Trip Class 02 - 60; J02 - J60; L00 - L60; or OFF
    • Overcurrent Trip Point (2 - 10 A) … MULT of 80 - 140% of CT primary
    • Address COM: C00 - C07; RS485: A01 - A99
    • Current Accuracy (%) ±3% (<100 A direct)
    • Current Unbalance Trip Point (%) 2 - 50% or 999 (disabled)
    • Ground Fault Accuracy (%) ±15%
    • Ground Fault Current Trip Point (A) (3 - 20) … MULT or 12 - 40% of CT primary or OFF
    • Humidity 10 - 95% non-condensing per IEC 68-2-3
    • Input AC Line Frequency (Hz) 50 / 60
    • Maximum Input Power 10
    • CT Ratio 1 - 10; 100; 150; 200; 300; 400; 500; 600; 700; 800
    • Output Load Rating (VA) Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 10 A @ 240 Vac
    • Overvoltage Trip Voltage (%) 172 - 528 V
    • Pollution Degree 3
    • Power Range Setting Power Scale: 1 = 0.01 - 0.99 kW; 2 = 1.00 - 9.95 kW; 3 = 10.0 - 99.5 kW; 4 = 100 - 650 kW; 5 = 0.01 - 1.32 hp; 6 = 1.34 - 13.3 hp; 7 = 13.4 - 133 hp; 8 = 134 - 871 hp; Low Power: 0.01 - 650 kW or 0.01 - 871 hp or 0 (off); LP setting is dependent on PWS setting; PWS must be set prior to LP setting
    • Protection Class IP20 (finger safe)
    • Rapid Cycle Timer (s) 0 - 999 s
    • Repeat Accuracy (%) Voltage: ±0.5% of nominal voltage; Current: ±1% (<100 A direct); Power: ±2%
    • Restart Delay Range All faults except undercurrent: 2 - 500 m; Undercurrent: 2 - 500 m A (Automatic); # of Restarts: All faults except undercurrent: 0; 1; oc1; 2; oc2; 3; oc3; 4; oc4; A; ocA (Automatic); Undercurrent: 0; 1; 2; 3; 4; A (Automatic)
    • Sensor Hole Size Max conductor size: 0.65 in (with insulation)
    • Short Circuit (kA) 100
    • Storage Temperature (F/C) -40° to 80°C (-40° to 176°F)
    • Surge Protection IEC: 61000-4-5 Level 3 2 kV line-to-line; Level 4 4 kV line-to-ground
    • Timing Accuracy (%) ±0.5 s
    • Undercurrent Trip Delay (s) 2 - 999 s (default)
    • Undervoltage Trip Voltage 170 - 524 V
    • Voltage Accuracy (%) ±1%
    • Voltage Unbalance Trip Point (%) 2 - 25% or 999 (disabled)
    • Datasheet
    • Check Stock Order Sample