background-waves

MP8000

Product Status| Activei

MP8000

Motor Overload Protection 8000 | Series: MP8000
info

The MP8000 is an advanced motor protection electronic overload relay that is fully programmable via Bluetooth® using an iPhone or Android smartphone/tablet with the Littelfuse app. It has an input voltage between 90–690 V ac and use of external PTs can extend the upper range above 690 V ac.

PropertyValue
Supply Voltage AC
85 - 264
Input Voltage (V)
90 - 690 Vac (use of external PTs can extend the upper range above 690 Vac)
Output Form
Control relay: SPST - Form A; Auxilliary relay: SPDT - Form C
Termination Type
Torque: Depluggable terminal blocks: 7 in-lbs; Earth ground: 7.9 in-lbs
Full Load Amp Range (A)
0.5 - 10 direct; 100+ (external CTs required)
Dimensions
2.91 H x 4.08 W x 4.79 D in. (73.9 x 103.6 x 121.7 mm)
Weight (kg)
0 Kg (kilogram)
Overcurrent Trip Class
02 - 60 or linear
Communications Interface
Bluetooth; Ethernet Modbus TCP/IP or Ethernet/IP
Communications Protocol
Ethernet Modbus TCP/IP or Ethernet/IP
Communications Range
Bluetooth range is up to 30 ft (range may be reduced depending on the smartphone/tablet used; enclosure type; or environmental factors)
Conformally Coated
Yes
Current Accuracy (%)
±2% (2 to 100 A direct)
Frequency (Hz)
50/60 Hz
Ground Fault Accuracy (%)
±2%
HP/kW Accuracy (%)
±5% of setting ±5 W
Humidity
10 - 95% non-condensing per IEC 68-2-3
Input AC Line Frequency (Hz)
50 / 60
Memory Capacity
Stores last 1000 faults with time and date stamp; includes conditions at time of trip
Output Load Rating (VA)
Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 5 A @ 240 Vac
Pollution Degree
3
Power Consumption
<5 W
Protection Class
IP20 (finger safe)
Repeat Accuracy (%)
Voltage: ±0.5% of nominal voltage; Current: ±1% (2 to 100 A direct)
Sensor Hole Size
Max conductor size: 0.63 in (with insulation)
Short Circuit (kA)
100 symmetrical at 690 V ac
Surge Protection
IEC: 61000-4-5 Level 3 2 kV line-to-line; Level 4 4 kV line-to-ground
Timing Accuracy (%)
2% ±0.5 s
Voltage Accuracy (%)
±1% of setting ±2 Vrms
Fast Transient Burst
IEC 61000-4-4; Level 3; 3.5 kV input power; Level 4; 4 kV line-to-ground
Electrostatic Discharge (ESD)
IEC 61000-4-2; Level 3; 6 kV contact; 8 kV air
FCC Certification Document Id
Part 15.107 for emissions; Part 15.247 for intentional radiators
Hi-Potential Test
Meets UL 508 (2 x rated V +1000 V for 1 minute)
Mounting Method
Surface mount (4 - #8 screws) or DIN rail mount
Operating Temperature Max (°C)
70
Operating Temperature Maximum Fahrenheit
158
Operating Temperature Minimum Celsius
-40
Operating Temperature Minimum Fahrenheit
-40
Radio Frequency Immunity (RFI), Conducted
IEC 61000-4-6; Level 3 10 V/m
Radio Frequency Immunity (RFI), Radiated
IEC 61000-4-3; Level 3 10 V/m
Storage Temperature Maximum Celsius
85
Storage Temperature Maximum Fahrenheit
185
Storage Temperature Minimum Celsius
-40
Storage Temperature Minimum Fahrenheit
-40

MP8000 Resources

Showing 1 to 1 of 1 Total Results
Share
Part NumberPart DescriptionRoHSPb-FreeRoHS (2015/863/EU) CertificateREACH (SVHC's) DeclarationREACH (SVHC's)Halogen FreeIPC-Material Declaration
MP8000Motor Overload Protection 8000

If the product environmental information that you are looking for does not appear in this tab, please complete the Product Environmental Information Request Form.