201 Voltage Relays

201-100-DPDT-60MS

  • Electrical Characteristics
    • Catalog # 201-100-DPDT-60MS
    • Input Voltage (V) 95 to 120VAC
    • Maximum Input Power 5W
    • Input AC Line Frequency (Hz) 50/60Hz
    • Output Form DPDT
    • Output Load Rating (VA) Pilot Duty: 480VA @ 240VAC; General Purpose: 10A @ 240VAC
    • Restart Delay Range After a Fault or Complete Power Loss: 60ms
    • Trip Delay Range Low Voltage: 0.5s; Unbalance Phasing Faults: 0.5s
    • Trip Point Accuracy (%) ±1%
    • Undervoltage Trip Voltage 90%
    • Undervoltage Reset Voltage (%) 93%
    • Voltage Unbalance Trip Point (%) 6%
    • Voltage Unbalance Reset (%) 4.50%
    • Termination Type Torque: 12 in-lbs; Wire: Stranded or solid 10-22AWG
    • Mounting Method DIN rail or surface mount (plug-in to OT11-PC socket)
    • Operating Temperature -40° to 70°C (-40° to 158°F)
    • Humidity 95% non-condensing per IEC 68-2-3
    • Dimensions 1.75 in H x 2.38 in W x 4.13 in D (44.5 x 60.3 x 104.8 mm)
    • Weight (lbs/g) 0.65 lb. (10.4 oz. 294.8 g)