202-200-SP

202-200-SP

  • Electrical Characteristics
    • Catalog # 202-200-SP
    • Input Voltage (V) 190 to 240VAC
    • Input Tolerance (%) ±10%
    • Maximum Input Power 5W
    • Input AC Line Frequency (Hz) 50/60Hz (50Hz will increase all delay timers by 20%.)
    • Output Form SPDT
    • Output Load Rating (VA) Pilot Duty: 480VA @ 240VAC; General Purpose: 10A @ 240VAC
    • Restart Delay Range After a Fault or Complete Power Loss: Manual 2 - 300s adjustable
    • Trip Delay Range Under/Over Voltage: 4s
    • Trip Point Accuracy (%) ±1%
    • Overvoltage Trip Voltage (%) 110%
    • Overvoltage Reset Voltage (%) 107%
    • Undervoltage Trip Voltage 90%
    • Undervoltage Reset Voltage (%) 93%
    • Termination Type 0.25 in male quick connect
    • Mounting Method 1/4 in socket head cap screw (customer supplied)
    • Operating Temperature -40° to 70°C (-40° to 158°F)
    • Humidity 95% non-condensing
    • Dimensions 2.50 in H x 2.50 in W x 1.40 in D (63.5 x 63.5 x 35.6 mm)
    • Weight (lbs/g) 0.5 lb. (8.0 oz. 226.8 g)